Analog inputs
All in all, the SA10 has 11 analog inputs. However, since our intention is to provide you with a test equipment that is user-friendly and circuit breaker-oriented, they have been preset to handle specific relevant functions such as coil and motor voltages, currents, analog motion transducers etc.
It is of course possible to set most of the inputs to handle other types of related input signals, such as pressure sensors or temperature sensors or any other type of analogue signal that may be relevant.

|
Static and dynamic resistance
As the only field test equipment on the market with a built-in micro ohm meter, it is a complete and versatile unit. It generates 200 ADC and the value is automatically recorded into the system together with your other measurements. In order to view the breaker pole's exact behavior during an operation, the dynamic resistance measurement function offers great diagnostic possibilities.
Communication
Standards RS232 communication is default. However, in order to comply with safety regulations a bluetooth communication kit is available, which allows the user to take his laptop pc and move up to 100 m (328 ft) away from the test-object.
|
Switch sync breakers
Upon switching for example capacitor banks, shunt reactors and power transformers it is common to use a switch-sync relay for the cb. The SA10 allows for full analysis of the point-on-wave switching technology.
First-trip or on-line analysis
In order to fully evaluate the condition of the circuit breaker mechanism, the SA10 provides inputs to test the breaker during an on-line operation. By doing that you can capture the "First Trip" of a breaker that has been stationary for a long time, and by that display how the breaker would perform in an actual fault situation. Both trip and close operations are possible on-line.
|